Several problems in thermodynamic calculation of surface air coolers.

[In Chinese. / En chinois.]

Author(s) : WANG L., MA J.

Type of article: Article

Summary

The article discusses the application of the two commonly used conclusions in the thermodynamic calculation of surface air coolers, i.e. "the same enthalpy of inlet air, the same enthalpy of outlet air" and "the mean coil surface state is on the line of the state points of the inlet and the outlet air". It verifies them according to the thermodynamic calculating formulas and points out that the mean coil surface state is approximatively existent under wet conditions. The article also discusses the shortcoming and rationality of the method of judging work conditions by mean coil surface state and it puts forward a method to judge work conditions of the fully dry, partially dry and fully wet. Analyses and demonstrates the method by a detailed calculation.

Available documents

Format PDF

Pages: 43-48

Available

  • Public price

    20 €

  • Member price*

    15 €

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: [In Chinese. / En chinois.]
  • Record ID : 2008-1319
  • Languages: Chinese
  • Source: HV & AC - vol. 37 - n. 205
  • Publication date: 2007/11

Links


See other articles in this issue (7)
See the source