Pompes à chaleur commerciales dans les applications chauffage d'eau sanitaire et récupération de la chaleur.

Commercial heat pumps for water heating and heat recovery.

Auteurs : NEKSÅ P., REKSTAD H., ZAKERI G. R., et al.

Résumé

Tap water heating is one promising application for a transcritical CO2 process. The temperature glide at heat rejection contributes to a very good temperature adaptation when heating tap water, which inherits a large temperature glide. A heating-COP of 4.3 is achieved for the prototype when heating tap water from 9 to 60 °C, at an evaporation temperature of 0 °C (seasonal performance factor of about 4 for an Oslo climate, using ambient air as the heat source). Thus, the primary energy consumption can be reduced by more than 75% compared with electrical heating. Hot water with temperatures up to 90 °C can be produced without operational difficulties.

Détails

  • Titre original : Commercial heat pumps for water heating and heat recovery.
  • Identifiant de la fiche : 2000-1751
  • Langues : Anglais
  • Source : CO2 technology in refrigeration, heat pump & air conditioning systems (with presentation of the results of the European JOULE/THERMIE Research Programme on CO2 heat pumping systems - COHEPS). Workshop proceedings.
  • Date d'édition : 18/03/1999
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres communications du même compte rendu (10)
Voir le compte rendu de la conférence