Recherche expérimentale sur la performance d’une pompe à bulles pour un transformateur de chaleur à diffusion-absorption.

Experimental research on the performance of a bubble pump for a diffusion absorption heat transformer.

Numéro : AB-SS-1032

Auteurs : WANG S., WANG Q., HE W., et al.

Résumé

The diffusion generation of the refrigerant and pumping process of the solution both happen in the bubble pump for a diffusion absorption heat transformer. This paper investigated the effect of diffusion generation of refrigerant and pumping performance of the bubble pump in an experimental setup. The influences of the motive head, the inner diameter of the lifting tube, temperature of vapor mixture and flow rate of diffusion gas on the performance were found. The flow rate of refrigerant increased more and more slowly with the increasing flow rate of diffusion gas while the pumping ratio decreased sharply. The lifting tube with small inner diameter,
high vapor mixture temperature and small motive head were suitable for the required small pumping ratio of bubble pump in a diffusion absorption heat transformer.

Détails

  • Titre original : Experimental research on the performance of a bubble pump for a diffusion absorption heat transformer.
  • Identifiant de la fiche : 30022726
  • Langues : Anglais
  • Source : International sorption heat pump conference, ISHPC 2017, Tokyo august 7-10.
  • Date d'édition : 07/08/2017

Liens


Voir d'autres communications du même compte rendu (159)
Voir le compte rendu de la conférence