Document IIF

Recherche expérimentale sur le R417A dans un système à pompe à chaleur utilisé pour chauffer de l'eau.

The experimental research of R417A in heat pump heating water system.

Auteurs : YAN Z., LI X., ZHANG L., et al.

Résumé

In a heat pump heating water system, R417A and R22 are employed as drop-in refrigerants in the authors' theoretical cycle numeral simulation and experiment study. The discharge temperature, power consumption, suction pressure, discharge pressure, refrigerant mass flow in the system have been tested under a few of different working conditions. The refrigeration and heating outputs and the value of COP have been calculated. The experiment results show that the actual operation results of R417A and R22 tally basically with theoretical simulations. The system operates in a normal way when replacing R22 with R417A without changing the lubricant. The discharge temperature of R417A is lower than that of R22, its power consumption decreases, heating output is less, but COP is a little higher than or equal to that of R22.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : The experimental research of R417A in heat pump heating water system.
  • Identifiant de la fiche : 2005-0423
  • Langues : Anglais
  • Source : 21st IIR International Congress of Refrigeration: Serving the Needs of Mankind.
  • Date d'édition : 17/08/2003

Liens


Voir d'autres communications du même compte rendu (398)
Voir le compte rendu de la conférence