IIR document

Two bed silica gel-water adsorption chillers: an effectual lumped parameter model.

Author(s) : WANG X. L., CHUA H. T.

Type of article: Article, IJR article

Summary

This article develops an improved lump-parameter design model to investigate the water-circulation heat recovery scheme as applied to the two-bed silica gel-water adsorption chillers. The authors demonstrate that performance predictions stemming from this improved lump-parameter formalism compare favorably with experimental results at various conditions, particularly at the industrial rated conditions. They find that the present lump-parameter formalism adequately elucidates the water-circulation heat recovery scheme as does the distributed-parameter formalism. In the studied working condition of a two-bed silica gel-water adsorption chiller, the differences in cooling capacities and COPs by using the two different formalisms are typically less than 10%. This gives rise to a useful and rapid design tool for the industry.

Available documents

Format PDF

Pages: 1417-1426

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Two bed silica gel-water adsorption chillers: an effectual lumped parameter model.
  • Record ID : 2008-0198
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 30 - n. 8
  • Publication date: 2007/12

Links


See other articles in this issue (17)
See the source