Régulation optimale de la pression du refroidisseur de gaz d'une pompe à chaleur au CO2 à l'aide de l'ouverture du détendeur électronique et de la vitesse du ventilateur externe, en mode refroidissement.

Optimal control of the gas-cooler pressure of a CO2 heat pump using EEV opening and outdoor fan speed in the cooling mode.

Auteurs : BAEK C., HEO J., JUNG J., et al.

Type d'article : Article, Article de la RIF

Résumé

The objective of this study is to investigate the control methods of the gas-cooler pressure in a CO2 heat pump. The cooling performance of the CO2 heat pump was measured by varying the refrigerant charge amount, EEV opening, compressor frequency, and outdoor fan speed at various outdoor temperatures. The effects of the EEV opening and the outdoor fan speed on the gas-cooler pressure and the COP were analyzed by using the experimental data. In the standard cooling condition at the compressor frequency of 45 Hz, the optimum gas-cooler pressure and the maximum COP were 9200 kPa and 3.04, respectively, at the optimum EEV opening of 41% and outdoor fan speed of 500 rpm. As the compressor frequency increased from 45 Hz to 55 Hz at the standard cooling condition, the optimum outdoor fan speed increased from 500 rpm to 700 rpm.

Documents disponibles

Format PDF

Pages : 1276-1284

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Optimal control of the gas-cooler pressure of a CO2 heat pump using EEV opening and outdoor fan speed in the cooling mode.
  • Identifiant de la fiche : 30008083
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 36 - n. 4
  • Date d'édition : 06/2013

Liens


Voir d'autres articles du même numéro (21)
Voir la source