Remplacement du R22 dans les équipements frigorifiques et de conditionnement d'air.
Alternative refrigerant to R22 in low-temperature and air-conditioning equipment.
Auteurs : FURUYAMA K., BANDOH Y., PENG L., et al.
Résumé
In a previous report, R32/125/134a/600 was proposed as an alternative refrigerant for replacing R22 in large-scale refrigeration-cycle systems to reach -30 °C. The authors tested the actual performance in equipment with a nominal cooling capacity of 30.2 kW designed for a 858 m3 refrigerated warehouse and a refrigeration- and Lorentz-cycle testing-apparatus with a 0.55 kW nominal energy consumption compressor under several temperature conditions of air-conditioning application. It was confirmed that cycle performance and the pressure conditions of R32/125/134a/600 were very similar to R22 and the actual performance of R32/125/134a/600 was better than that of R22.
Détails
- Titre original : Alternative refrigerant to R22 in low-temperature and air-conditioning equipment.
- Identifiant de la fiche : 2003-1140
- Langues : Anglais
- Source : 2002 Purdue conferences. 2002 compressor engineering & refrigeration and air conditioning conferences at Purdue [CD-ROM].
- Date d'édition : 16/07/2002
- Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.
Liens
Voir d'autres communications du même compte rendu (64)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
HCFC;
HFC;
Hydrocarbures;
Mélanges - Mots-clés : R134a; Butane; Basse température; R32; R22; R125; Substitut; Mélange; Frigorigène; Conditionnement d'air
-
Determination of the performance, leak scenario...
- Auteurs : ROBERTS N. A.
- Date : 14/07/1998
- Langues : Anglais
- Source : Proceedings of the 1998 Purdue International Refrigeration Conference.
Voir la fiche
-
Alternative drop-in in refrigerant to R22 for r...
- Auteurs : BANDOH Y., FURUYAMA K., SAITO M., et al.
- Date : 04/12/2002
- Langues : Anglais
- Source : Green breeze from Asia: frontiers of refrigerants, heat transfer and system.. ACRA-2002. Proceedings of the Asian conference on refrigeration and air conditioning.
Voir la fiche
-
High efficiency R22 replacement.
- Auteurs : ROBERTS N. A., PEARSON S. F.
- Date : 23/07/1996
- Langues : Anglais
Voir la fiche
-
Energy efficiency potential of HCFC-22 alternat...
- Auteurs : BIVENS D. B., DENISON G.
- Date : 22/09/1996
- Langues : Anglais
- Source : Heat pumping technologies towards the next century: applications and markets. Proceedings of the 5th IEA Conference.
Voir la fiche
-
Thermodynamic evaluation of R22 alternative ref...
- Auteurs : DOMANSKI P. A., DIDION D. A.
- Date : 1993
- Langues : Anglais
- Source : ASHRAE Transactions.
Voir la fiche