Résistance de la surface extérieure : projet d'une nouvelle valeur de référence dans le bâtiment.

Outside surface resistance: proposed new value for building design.

Auteurs : LOVEDAY D. L., TAKI A. H.

Type d'article : Article

Résumé

Findings of outdoor full-scale experimental studies show that the experimentally measured values for the convection coefficient are significantly higher than the values assumed in current design guidance. An expression derived from four full-scale investigations is presented. A modified design value for the external surface resistance is proposed for the condition of "normal" exposure to replace the current value of 0.06. As a result, it is recommended that the corresponding U-value for single glazing be raised to 6.3 watts/m2.K from its currently accepted value of 5.6.

Détails

  • Titre original : Outside surface resistance: proposed new value for building design.
  • Identifiant de la fiche : 1999-0366
  • Langues : Anglais
  • Source : Build. Serv. Eng. Res. Technol. - vol. 19 - n. 1
  • Date d'édition : 1998
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (5)
Voir la source