Simulation à l'aide de la dynamique des fluides numérisée de la concentration des impuretés gazeuses dans un atelier industriel typique à Hong-Kong.

CFD simulation of concentration of gaseous impurities in a typical Hong Kong industrial workshop.

Auteurs : LIN Z., CHOW T. T., FONG K. F., et al.

Résumé

A validated CFD model was employed to generate concentration distribution data for CO2, radon and moisture in a typical Hong Kong industrial workshop with displacement ventilation. The indoor radon comes from building materials. The indoor CO2 and moisture are from the occupants. Because the upward free convection around a person brings the air from a lower level to the breathing zone, the inhaled air is cleaner than the air at the same height. Prediction of contaminant distribution is more difficult than air temperature and flow distribution.

Détails

  • Titre original : CFD simulation of concentration of gaseous impurities in a typical Hong Kong industrial workshop.
  • Identifiant de la fiche : 2002-0469
  • Langues : Anglais
  • Source : Air distribution in rooms: ventilation for health and sustainable environment. Roomvent 2000. Proceedings of the 7th international conference.
  • Date d'édition : 09/07/2000
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres communications du même compte rendu (67)
Voir le compte rendu de la conférence