Simulation dynamique d'un refroidisseur à absorption au LiBr-eau, à écoulement parallèle à double effet.

Dynamic simulation of a double-effect parallel-flow LiBr-water absorption chiller.

Auteurs : LIN P., WANG R. Z., WU J. Y.

Résumé

A dynamic model of a double effect parallel-flow LiBr-water absorption chiller has been developed. Lumped parameter method has been used for the main components to form their mass and energy conservation equations. A 20% linear change of external conditions during 1000 s has been added to the model to investigate the dynamic behaviour of the chiller. The dynamic simulation results show that it takes about 50 minutes for the chiller to achieve a new steady-state. External and internal heat transfer process and the characteristics of thermal mass have great influences on the system's dynamic behaviour.

Détails

  • Titre original : Dynamic simulation of a double-effect parallel-flow LiBr-water absorption chiller.
  • Identifiant de la fiche : 2009-0164
  • Langues : Anglais
  • Source : Cryogenics and refrigeration. Proceedings of ICCR'2008.
  • Date d'édition : 05/04/2008