Document IIF

Simulation numérique de l'écoulement dans les tours de refroidissement humides à contre-courant.

Numerical simulation of counter-flow wet-cooling towers.

Auteurs : HEIDARINEJAD G., KARAMI M., DELFANI S.

Type d'article : Article, Article de la RIF

Résumé

Cooling towers are used to cool a warm water stream through evaporation of part of the water into an air stream. A cooling tower consists of three zones; namely spray, packing and rain zones. In cooling towers, a significant portion of the total heat rejected may occur in the spray and rain zones. These zones are modelled and solved numerically using a computer code. The developed models of these zones are validated against experimental data. For the case study under consideration, the error in calculation of the tower volume is 1.5% when the spray and rain zones are neglected. This error is reduced to 1.1 and 0.25% as the spray and rain zones are incorporated in the model, respectively. Furthermore, the effect of the Lewis factor on the performance prediction of wet-cooling towers is investigated using Bosnjakovic equation.

Documents disponibles

Format PDF

Pages : 996-1002

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Numerical simulation of counter-flow wet-cooling towers.
  • Identifiant de la fiche : 2009-1506
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 32 - n. 5
  • Date d'édition : 08/2009

Liens


Voir d'autres articles du même numéro (38)