Système frigorifique innovant fonctionnant en cascade à absorption-compression basse température.

A novel low-temperature absorption–compression cascade refrigeration system.

Auteurs : XU Y., CHEN F., WANG Q., et al.

Type d'article : Article

Résumé

This paper presents a novel absorption–compression cascade refrigeration system, which can reach an evaporating temperature of -170°C. In the cascade system, the refrigerant of compression subsystem (CS) is subcooled by the refrigerant of low-grade heat driven absorption subsystem (AS) to reduce the electric power consumption. Theoretical and experimental investigations were carried out over the CS evaporating temperature ranging from -100 to -170°C and operating parameters were given. At the CS evaporating temperature of -170°C, when AS provided a low-grade cooling capacity of 164.8 W to CS, a decrease of 2.5°C in CS evaporating temperature or an increase of 32.3 W in high-grade cooling capacity of CS were observed. Meanwhile, in CS, the discharge temperature and pressure decreased, while the suction pressure increased. These beneficial results not only verified the feasibility of the system, but also revealed the application potential of the system in the future.

Détails

  • Titre original : A novel low-temperature absorption–compression cascade refrigeration system.
  • Identifiant de la fiche : 30015176
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 75
  • Date d'édition : 22/01/2015
  • DOI : http://dx.doi.org/10.1016/j.applthermaleng.2014.10.043