Based on field data from a medium scale ammonia based milk refrigeration plant located in northern part of India, a trans-critical CO2 based heat pump system is conceptualized to utilize the waste heat from the plant to improve overall coefficient of performance. Year round plant operating data is collected. The plant handles in the range of 0.1 to 0.15 million liters of milk and milk products daily. It maintains two cooling chambers, one at 4°C and the other at -10°C. Every seven days it is required to replenish a 5000 liter tank with ground water for evaporative cooling of the system. Up-stream and down-stream processes in the milk processing plant utilizes a coal fired boiler system which also uses ground water. In this study, the condenser of the ammonia based refrigeration system is coupled with the evaporator of the proposed CO2 trans-critical heat pump system which is maintained at 20°C round the year. The heat pump delivers heat at about 70°C to pre heat the boiler feed water available in temperature range 25° to 29°C round the year. Augmentation of the proposed CO2 system is able to reduce coal consumption by utilizing the waste heat from the ammonia system at the same time reduce ground water utilization by eliminating evaporative cooling. The proposed heat pump system has encouraging COP and is designed to be largely independent of variation in ambient temperature. Based on field data, a comparative study is carried out using thermodynamic & thermo-economic analysis for a duration of one year to establish feasibility of the proposed system.
Documents disponibles
Format PDF
Pages : 9 p.
Disponible
Prix public
20 €
Prix membre*
15 €
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : A trans-critical CO2 heat pump system for waste heat utilization in warm weather condition applied to a milk refrigeration plant.
- Identifiant de la fiche : 30018593
- Langues : Anglais
- Source : 2016 Purdue Conferences. 16th International Refrigeration and Air-Conditioning Conference at Purdue.
- Date d'édition : 11/07/2016
Liens
Voir d'autres communications du même compte rendu (274)
Voir le compte rendu de la conférence
Indexation
-
Low-grade industrial waste heat recovery with C...
- Auteurs : MINEA V.
- Date : 25/06/2012
- Langues : Anglais
- Source : 10th IIR-Gustav Lorentzen Conference on Natural Working Fluids (GL2012). Proceedings. Delft, The Netherlands, June 25-27, 2012.
- Formats : PDF
Voir la fiche
-
Performance analysis of a CO2 based ...
- Auteurs : SINGHA P., VAISHAK S., DASGUPTA M. S., BHATTACHARYYA S., HAFNER A., ELARGA H.
- Date : 21/08/2023
- Langues : Anglais
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Formats : PDF
Voir la fiche
-
Energy and exergy analysis of transcritical CO<...
- Auteurs : KONG L., WALMSLEY T. G., ABU KHASS O., SCHLOSSER F., CLELAND D. J., CHEN Q., HOANG D., CARSON J. K.
- Date : 21/08/2023
- Langues : Anglais
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Formats : PDF
Voir la fiche
-
CO2 heat pump for waste heat recovery and utili...
- Auteurs : SINGH S., DASGUPTA M. S.
- Date : 06/2017
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 78
- Formats : PDF
Voir la fiche
-
Increasing the energy efficiency of a dairy by ...
- Auteurs : KOSTER L., BENGSCH J., SVENDSEN E. S., WIDELL K. N., JENSSEN S.
- Date : 11/06/2024
- Langues : Anglais
- Source : 8th IIR International Conference on Sustainability and the Cold Chain. Proceedings: June 9-11 2024
- Formats : PDF
Voir la fiche