Document IIF
Temps de cycle modifié afin d'améliorer la performance des refroidisseurs à adsorption à deux lits.
A new cycle time allocation for enhancing the performance of two-bed adsorption chillers.
Auteurs : MIYAZAKI T., AKISAWA A., SAHA B. B., et al.
Type d'article : Article, Article de la RIF
Résumé
This study proposes a new cycle time allocation in silica gel-water based adsorption chillers to enhance their performances. The new cycle time allocation not only improves the cooling capacity and COP, but also contributes in the reduction of delivered chilled water fluctuations. In a conventional adsorption chiller operation, the appropriate preheating/precooling process enhances the cooling capacity, whereas the excess pre-heating/pre-cooling time abates the average cooling capacity. The proposed new cycle time allocation allows the continuous cooling effect over the cycle without sacrificing the effect of preheating/precooling. Simulation results showed that the new cycle time was effective for both RD type silica gel-water and CaCl2-in-silica gel-water pairs, and the cooling capacity was increased as much as by 6%.
Documents disponibles
Format PDF
Pages : 846-853
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : A new cycle time allocation for enhancing the performance of two-bed adsorption chillers.
- Identifiant de la fiche : 2009-1568
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 32 - n. 5
- Date d'édition : 08/2009
Liens
- Liens externes :
Voir d'autres articles du même numéro (38)
Voir la source
Indexation
- Thèmes : Systèmes à absorption et adsorption
- Mots-clés : Gel de silice; Amélioration; Adsorption; Système à adsorption; Simulation; Procédé; Eau
-
On the linear driving force approximation for a...
- Auteurs : SHARKAWY I. I. el-
- Date : 05/2011
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 34 - n. 3
- Formats : PDF
Voir la fiche
-
Two bed silica gel-water adsorption chillers: a...
- Auteurs : WANG X. L., CHUA H. T.
- Date : 12/2007
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 30 - n. 8
- Formats : PDF
Voir la fiche
-
Effect of regeneration conditions on the adsorp...
- Auteurs : CHANG K. S., WANG H. C., CHUNG T. W.
- Date : 04/2004
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 24 - n. 5-6
Voir la fiche
-
Static analysis of a new scheme of two stage re...
- Auteurs : AKISAWA A., UMAIR M., ENOKI K., et al.
- Date : 08/2018
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 92
- Formats : PDF
Voir la fiche
-
Cycle à adsorption à récupération de masse à mu...
- Auteurs : KHAN M. Z. I., SAHA B. B., ALAM K. C. A., et al.
- Date : 2006
- Langues : Japonais
- Source : Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 23 - n. 4
Voir la fiche