Document IIF

Transfert de chaleur lors de l'ébullition du dioxyde de carbone à l'intérieur d'un tube à microailettes de faible diamètre

Flow boiling heat transfer of carbon dioxide inside a small-sized microfin tube.

Auteurs : DANG C., HARAGUCHI N., HIHARA E.

Type d'article : Article, Article de la RIF

Résumé

This study investigates the flow boiling heat transfer of carbon dioxide inside a small-sized microfin tube (mean inner diameter: 2.0 mm; helix angle: 6.3°) at a saturation temperature of 15°C, and heat and mass flux ranges of 4.5-18 kW/m2 and 360-720 kg/m2.s, respectively. Although, experimental results indicated that heat flux has a significant effect on the heat transfer coefficient, the coefficient does not always increase with mass flux, as in the case of conventional refrigerants such as HFCs or HCFCs. Under certain conditions, the heat transfer coefficient at a high mass flux was lower than that at a lower mass flux, indicating that convective heat transfer had a suppression effect on nucleate boiling. The heat transfer coefficients in the microfin tubes were 1.92.3 times the values in smooth tubes of the same diameter under the same experimental conditions, and the dryout quality was much higher, ranging from 0.9 to 0.95. The experimental results indicated that using microfin tubes may considerably increase the overall heat transfer performance.

Documents disponibles

Format PDF

Pages : pp. 655-663

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Flow boiling heat transfer of carbon dioxide inside a small-sized microfin tube.
  • Identifiant de la fiche : 2010-0401
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 33 - n. 4
  • Date d'édition : 06/2010

Liens


Voir d'autres articles du même numéro (23)
Voir la source