Un modèle de prévision semi-empirique pour la température de la ligne de refoulement de compresseurs hermétiques.

A semi empirical prediction model for the discharge line temperature of hermetic compressors.

Numéro : pap. 1242

Auteurs : MYSZKA D. H., GUAN C., MURRAY A. P., et al.

Résumé

Predicting the discharge line temperature (DLT) of air conditioning and refrigeration compressors is important to ensure sufficient lubricant properties and proper performance of components that are positioned in the exhaust stream. Understanding the DLT is also necessary for the design of waste heat recovery systems, which are of increasing interest. However, compressor performance information published by manufacturers does not typically include DLT values. Assumptions made in established thermodynamic models result in only modest correlation between predicted and observed DLT values. Numerous comprehensive DLT prediction models have been developed with excellent accuracy, but require many details of a particular compressor. This paper presents an assessment of various thermodynamic DLT prediction methods that do not rely on individual compressor-specific parameters. Prediction methods considered include an entropy-based model, a polytropic model and an energy model. The energy model was expanded to include an empirical component to account for high-side heat transfer and exhibits an accuracy that significantly exceeds the other established methods. The model was evaluated for both traditional refrigeration and air-conditioning operating conditions and translates well to vapor-injected, economizer cycles. Lastly, a study was conducted to determine the robustness of the empirical component by analyzing the relationship between the accuracy of the model and the number of experimental points used to produce the model.

Documents disponibles

Format PDF

Pages : 9 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : A semi empirical prediction model for the discharge line temperature of hermetic compressors.
  • Identifiant de la fiche : 30013985
  • Langues : Anglais
  • Source : 2014 Purdue Conferences. 22nd International Compressor Engineering Conference at Purdue.
  • Date d'édition : 14/07/2014

Liens


Voir d'autres communications du même compte rendu (138)
Voir le compte rendu de la conférence