Une analyse expérimentale d'une installation de supermarché fonctionnant au dioxyde de carbone.

An experimental analysis of a supermarket plant working with carbon dioxide as the refrigerant.

Auteurs : CECCHINATO L., CORRADI M., MINETTO S., et al.

Résumé

This paper presents the experimental results of a commercial refrigeration plant for supermarkets working with R-744. The system was installed for testing purpose in a test area, simulating a 300 m2 supermarket. The system has a total capacity of 31 kW in medium temperature (MT - evaporation temperature -10°C) and about 15 kW in low temperature (LT - evaporation temperature -35°C). The swept volume of the compressors is 5.4 m3/h for MT and 5.9 m3/h for LT, the MT and the LT circuits are completely separated. The MT unit has two single stage compressors in parallel, while the LT unit has two compressors in parallel of two-stage internal compound type. In both LT and MT units on the high pressure side, the heat is rejected to water. The throttling system includes a differential valve or a step-motor electronic valve (acting as a controlled back-pressure valve) in alternative, coupled with a liquid receiver and thermostatic electronic valves as the final stage. The experimental tests were run, both in subcritical and transcritical conditions, using the two valves varying the gas-cooler water inlet temperature from 15 to 35°C. Different settings of the differential valve spring were used.

Documents disponibles

Format PDF

Pages : ICR07-D1-1062

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : An experimental analysis of a supermarket plant working with carbon dioxide as the refrigerant.
  • Identifiant de la fiche : 2008-0506
  • Langues : Anglais
  • Source : ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
  • Date d'édition : 21/08/2007

Liens


Voir d'autres communications du même compte rendu (839)
Voir le compte rendu de la conférence