Document IIF

Une étude expérimentale du mélange de frigorigènes R32/R290 pour remplacement direct (drop-in) du HFC410A dans les conditionneurs d'air domestiques.

An experimental investigation of refrigerant mixture R32/R290 as drop-in replacement for HFC410A in household air conditioners.

Auteurs : TIAN Q., CAI D., REN L., et al.

Type d'article : Article, Article de la RIF

Résumé

In the present paper, the refrigerant mixture R32/R290 (68%/32% by weight) is investigated as the drop-in replacement for R410A in household air conditioners. The GWP of it is only 22% of that of R410A. Theoretical and experimental investigations are conducted on the performance of the air conditioners working with both R32/R290 and R410A. Experimental results show that the refrigerant charge amount of R32/R290 is reduced by 30.0%–35.0%; the cooling and heating capacities are increased by 14.0%–23.7%. For further reducing charge amount and flammability, the micro-channel heat exchanger (condenser) is employed to replace the finned tube one. Compared with the R32/R290 system using finned tube heat exchanger, the R32/R290 charge amount and the power consumption are reduced by 34.1% and 0.4%, respectively; the cooling capacity and the COP are increased by 6.4% and 6.8%, respectively.

Documents disponibles

Format PDF

Pages : 216-228

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : An experimental investigation of refrigerant mixture R32/R290 as drop-in replacement for HFC410A in household air conditioners.
  • Identifiant de la fiche : 30015233
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 57
  • Date d'édition : 09/2015

Liens


Voir d'autres articles du même numéro (25)
Voir la source