Une évaluation énergétique d'un système frigorifique au CO2 fonctionnant sous conditions surcritiques et sous-critiques.
Energetic evaluation of a CO2 refrigeration plant working in supercritical and subcritical conditions.
Auteurs : SÁNCHEZ D., PATIÑO J., SANZ-KOCK C., et al.
Type d'article : Article
Résumé
Unlike other refrigerants, R744 (or carbon dioxide) has a very low critical temperature (30.98°C) which hampers working in subcritical conditions especially when the environment is used as a heat rejection sink. Accordingly, CO2 refrigeration plants are designed to work in supercritical conditions. Notwithstanding, the heat rejection temperature may decrease below the critical one during long periods of time (for example in winter or autumn), thereby offering the possibility of operating in subcritical conditions.
According with this and in order to give useful information for related system design and operation, the aim of this paper is to analyse the behaviour of a CO2 refrigeration plant designed for supercritical conditions when it works in subcritical conditions. To achieve this objective a series of experimental assays has been performed. The results obtained shown a decrease in the coefficient of performance (COP) and cooling capacity View the MathML source(Q?ev) if the heat exchanger designed as a gas-cooler operates as a condenser in some cases. To avoid this, a possible solution is proposed consists on using an inverter drive to reduce the refrigerant mass flow rate in order to enhance the gas-cooler/condenser thermal effectiveness. From the experimental results obtained, it could be remarked that if the heat exchanger is designed as a condenser and operates as a gas-cooler, the energy performance of the refrigeration plant could improve under certain subcritical and supercritical conditions.
Détails
- Titre original : Energetic evaluation of a CO2 refrigeration plant working in supercritical and subcritical conditions.
- Identifiant de la fiche : 30011594
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 66 - n. 1-2
- Date d'édition : 05/2014
- DOI : http://dx.doi.org/10.1016/j.applthermaleng.2014.02.005
Liens
Voir d'autres articles du même numéro (17)
Voir la source
Indexation
-
Thèmes :
Systèmes à compression;
CO2 - Mots-clés : État supercritique; Système frigorifique; Énergie; Refroidisseur de gaz; R744; Performance; Condenseur; CO2
-
CO2 als Kältemittel. 2. Gaskühler und Mitteldru...
- Auteurs : BACHMANN S.
- Date : 02/2010
- Langues : Allemand
- Source : Kälte + Klimatechnik (Die) - vol. 63 - n. 2
Voir la fiche
-
CO2 refrigeration: a revolution in the making? ...
- Auteurs : ALDER G.
- Date : 11/2004
- Langues : Anglais
- Source : Afr. Heat. Cool. - vol. 5 - n. 4
Voir la fiche
-
Study on carbon dioxide gas cooler heat transfe...
- Auteurs : HIHARA E., WANG J.
- Date : 11/2002
- Langues : Anglais
- Source : Int. J. Energy Res. - vol. 26 - n. 14
Voir la fiche
-
The performance analysis of a two-stage transcr...
- Auteurs : ÖZGÜR A. E.
- Date : 2008
- Langues : Anglais
- Source : Int. J. Energy Res. - vol. 32
Voir la fiche
-
Effect of heat conduction through the fins of a...
- Auteurs : PARK C. Y., HRNJAK P.
- Date : 05/2007
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 30 - n. 3
- Formats : PDF
Voir la fiche