Utilisation d'un système déshydratant intégré au cycle à air du système de refroidissement pour l'usage simultané en supermarché : froid et conditionnement d'air avec ventilation.
Using an air cycle refrigerator integrated desiccant system for simultaneous usage in supermarkets: refrigerating and ventilated air conditioning.
Auteurs : ELSAYED E. S., AKISAWA A., KASHIWAGI T., et al.
Résumé
The study numerically investigated the performance of an air cycle refrigerator integrated desiccant system used in supermarket applications. The cooling effect of the cycle is used to refrigerate the display cases and the exhausted heat from the air cycle is used to regenerate the desiccant rotor to dehumidify the ventilated air in summer and to heat this air in winter. Simulation analysis is carried out to calculate the air conditioning coefficient of performance (COPac), refrigerating coefficient of performance (COPr), supply air conditions and the supply temperature to the display cases under different conditions. From the results, it has been clarifying that the system can operate at a wide range of refrigeration temperature with a small change on COPr, the desiccant system has the ability to supply air at low humidity removing a large latent load in summer and using the heat rotor to recovery the exhausted energy from the store area significantly increases COPac of the system especially in winter.
Détails
- Titre original : Using an air cycle refrigerator integrated desiccant system for simultaneous usage in supermarkets: refrigerating and ventilated air conditioning.
- Identifiant de la fiche : 2007-0197
- Langues : Anglais
- Source : ACRA-2006. Proceedings of the 3rd Asian conference on refrigeration and air conditioning.
- Date d'édition : 21/05/2006
Liens
Voir d'autres communications du même compte rendu (161)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
Equipements d'humidification/déshumidification;
Supermarchés, meubles de vente;
Systèmes à éjection, cycle à air, cycle Stirling, autres cycles - Mots-clés : Système frigorifique; Calcul; Roue déshydratante; Air; Supermarché; Performance; Échangeur rotatif; Déshydratation; Cycle thermodynamique; COP
-
Using an air cycle refrigerator integrated desi...
- Auteurs : ELSAYED E. S., AKISAWA A., KASHIWAGI T., et al.
- Date : 21/05/2006
- Langues : Anglais
- Source : ACRA-2006. Proceedings of the 3rd Asian conference on refrigeration and air conditioning.
Voir la fiche
-
A novel IMS-ejector based supermarket CO2<...
- Auteurs : SENGUPTA A., DASGUPTA M. S.
- Date : 27/04/2023
- Langues : Anglais
- Source : 10th IIR Conference on Ammonia and CO2 Refrigeration Technologies.
- Formats : PDF
Voir la fiche
-
Analysis of heat recovery system for air-condit...
- Auteurs : BUTRYMOWICZ D., KEDZIERSKI M., SMIERCIEW K., et al.
- Date : 24/08/2019
- Langues : Anglais
- Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
Voir la fiche
-
Performance analysis of advanced air cycle refr...
- Auteurs : HWANG K., HYUN S., ANDO T.
- Date : 17/08/2003
- Langues : Anglais
- Source : 21st IIR International Congress of Refrigeration: Serving the Needs of Mankind.
- Formats : PDF
Voir la fiche
-
Comparative study of various supermarket refrig...
- Auteurs : GULLO P., PUROHIT N., SANKARDASGUPTA M., et al.
- Date : 06/04/2018
- Langues : Anglais
- Source : 5th IIR International Conference on Sustainability and the Cold Chain. Proceedings: Beijing, Chine, 6-8 avril 2018
- Formats : PDF
Voir la fiche