Amélioration de la distribution d'air des armoires de serveurs de type fermées à l'aide de chicanes d'écoulement.

Air distribution improvement of closed type server cabinets using flow baffles.

Numéro : pap. n. 54

Auteurs : CHEN H. Y., CHUAH Y. K., HSIEH M. H., et al.

Résumé

This paper addresses the problems of airflow in the narrow cold and hot passages of a close type server cabinet. The problems of flow distribution and recirculation could lead to hotter air mixed into the cool air supplied to the servers. Flow baffles are evaluated for isolation of cold and hot passages, and minimize the air flowing between the servers. Computer models were set up to study the flow and temperature fields. Supply heat index (SHI) that indicates the enthalpy rise due to warm air infiltration into the cool air was used in the performance evaluation. The simulation results show flow baffles could improve on the flow distribution. Compared with the base case with SHI 0.29, the flow baffles can reduce SHI to 0.03. It was concluded that flow baffles are viable solution to the problems of hot air mixing into cold air in close server cabinets.

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Air distribution improvement of closed type server cabinets using flow baffles.
  • Identifiant de la fiche : 30015089
  • Langues : Anglais
  • Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
  • Date d'édition : 16/08/2015
  • DOI : http://dx.doi.org/10.18462/iir.icr.2015.0054

Liens


Voir d'autres communications du même compte rendu (657)
Voir le compte rendu de la conférence