Améliorations du cycle frigorifique transcritique biétagé à détente par éjecteur au CO2.

Cycle improvements to ejector-expansion transcritical CO2 two-stage refrigeration cycle.

Auteurs : YARI M., SIROUSAZAR M.

Type d'article : Article

Résumé

It was found that, compared with the conventional transcritical CO2 cycle and ejector-expansion transcritical CO2 cycle, the simulation results show that the coefficient of performance and second law efficiency of the new cycle were increased by about 55.5 and 26%, respectively, under the operating conditions that evaporator temperature is 10°C; gas cooler outlet temperature is 40°C and gas cooler pressure is optimum pressure.

Détails

  • Titre original : Cycle improvements to ejector-expansion transcritical CO2 two-stage refrigeration cycle.
  • Identifiant de la fiche : 2010-0785
  • Langues : Anglais
  • Source : Int. J. Energy Res. - vol. 32 - n. 7
  • Date d'édition : 2008
  • DOI : http://dx.doi.org/10.1002/er.1385