Cycle improvements to ejector-expansion transcritical CO2 two-stage refrigeration cycle.

Author(s) : YARI M., SIROUSAZAR M.

Type of article: Article

Summary

It was found that, compared with the conventional transcritical CO2 cycle and ejector-expansion transcritical CO2 cycle, the simulation results show that the coefficient of performance and second law efficiency of the new cycle were increased by about 55.5 and 26%, respectively, under the operating conditions that evaporator temperature is 10°C; gas cooler outlet temperature is 40°C and gas cooler pressure is optimum pressure.

Details

  • Original title: Cycle improvements to ejector-expansion transcritical CO2 two-stage refrigeration cycle.
  • Record ID : 2010-0785
  • Languages: English
  • Source: Int. J. Energy Res. - vol. 32 - n. 7
  • Publication date: 2008
  • DOI: http://dx.doi.org/10.1002/er.1385

Links


See the source