In this paper, we analyze the refrigerant‐side temperature profiles in the coil of an air‐to‐water heat pump. The heat pump unit uses R410A as refrigerant and it works following a flash tank vapor injection cycle (using a vapor‐injected compressor). Its main components are a coil as the outdoor heat exchanger, a four‐way reversing valve, electronic expansion valves, a plate heat exchanger as the indoor heat exchanger, and a variable speed compressor.
The coil consists of 5 refrigerant circuits arranged one on top of the other. Each circuit is made up of 7 hairpins (14 tubes per circuit) and all have similar lengths. In order to estimate the refrigerant temperature profiles in the circuitry of the coil, 48 temperature sensors were attached on the refrigerant tubes of the coil.
Experiments were performed at different compressor and air fan speed values with the heat pump unit working in the cooling mode of operation. Results suggest that refrigerant distribution is not uniform through each circuit and that some refrigerant accumulation occurs in the lower refrigerant circuits. This refrigerant maldistribution seems to be higher when decreasing the compressor speed, but it is not affected by the air‐fan speed.
Documents disponibles
Format PDF
Pages : 12
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Analysis of the refrigerant‐side temperature profiles in the coil of an air-to‐water heat pump.
- Identifiant de la fiche : 30031821
- Langues : Anglais
- Sujet : Technologie
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Date d'édition : 21/08/2023
- DOI : http://dx.doi.org/10.18462/iir.icr.2023.0675
Liens
Voir d'autres communications du même compte rendu (491)
Voir le compte rendu de la conférence
-
Modelling of an air-to-water heat pump, equippe...
- Auteurs : DARDENNE L., FRACCARI E., MAGGIONI A., et al.
- Date : 02/09/2013
- Langues : Anglais
- Source : Compressors 2013: 8th International Conference on Compressors and Coolants.
- Formats : PDF
Voir la fiche
-
Some aspects of the vapour injection in the hea...
- Auteurs : CEJKA Z.
- Date : 02/09/2009
- Langues : Anglais
- Source : Compressors 2009: 7th International Conference on Compressors and Coolants
- Formats : PDF
Voir la fiche
-
Comparison of the heating performance of an inv...
- Auteurs : ROH C. W., KIM M. S.
- Date : 03/2012
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 35 - n. 2
- Formats : PDF
Voir la fiche
-
Modelling of an air-to-water heat pump, equippe...
- Auteurs : DARDENNE L., FRACCARI E., MAGGIONI A., et al.
- Date : 02/09/2013
- Langues : Anglais
- Source : Compressors 2013: 8th International Conference on Compressors and Coolants.
- Formats : PDF
Voir la fiche
-
Study on performance of a heat pump water heate...
- Auteurs : CAO F., FEI J., XING Z., et al.
- Date : 10/2009
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 29 - n. 14-15
Voir la fiche