COMPARAISON DE DEUX STRATEGIES DE REGULATION POUR SIMULER LA PERFORMANCE A CHARGE PARTIELLE D'UNE INSTALLATION DE CONDITIONNEMENT D'AIR SIMPLE.

COMPARISON OF TWO CONTROL STRATEGIES TO SIMULATE PART-LOAD PERFORMANCE OF A SIMPLE AIR-CONDITIONING SYSTEM.

Résumé

LA DERIVATION DE L'AIR DE L'EVAPORATEUR ET LA MODIFICATION DU DEBIT D'EAU GLACEE SONT DES MOYENS COURANTS DE REGULATION DE LA TEMPERATURE DES LOCAUX DANS LES INSTALLATIONS DE CONDITIONNEMENT D'AIR LORS DU FONCTIONNEMENT A CHARGE PARTIELLE. CELA PROVOQUE QUELQUEFOIS DES MODIFICATIONS DE L'HUMIDITE RELATIVE. CETTE SITUATION A ETE ETUDIEE EN UTILISANT UN MODELE AMELIORE DE MICROORDINATEUR. ON A CONSIDERE DEUX STRATEGIES DE REGULATION : 1. MODULATION DU DEBIT D'EAU GLACEE ET 2. VARIATION DE LA PROPORTION D'AIR DERIVE. BIEN QUE LA CHARGE DE L'EVAPORATEUR FUT SUPERIEURE D'A PEU PRES 11 % AVEC LA REGULATION SUR DE L'AIR DE DERIVATION EN COMPARAISON DE LA REGULATION SUR L'EAU GLACEE POUR LES CHARGES PARTIELLES CONSIDEREES, ON OBTENAIT AVEC LA PREMIERE UNE BIEN MEILLEURE REGULATION DE L'HUMIDITE RELATIVE ET DU CONFORT.

Détails

  • Titre original : COMPARISON OF TWO CONTROL STRATEGIES TO SIMULATE PART-LOAD PERFORMANCE OF A SIMPLE AIR-CONDITIONING SYSTEM.
  • Identifiant de la fiche : 1988-2428
  • Langues : Anglais
  • Date d'édition : 1987
  • Source : Source : ASHRAE Trans.
    vol. 93; n. 2; 1768-1780; 11 fig.; 12 ref.