Document IIF

Conception d'un système de refroidissement cryogénique pour les aimants FT-ICR de 21 tonnes.

Design of cryogenic cooling system for 21 T FT-ICR magnets.

Auteurs : CHOI Y. S., KIM D. L., LEE B. S., et al.

Résumé

A new concept of cooling system for 21 T FT-ICR magnets is presented. The magnets will be built horizontally in order to accomplish the requirement of user friendliness and reliability, and the replenishment of liquid helium will not be necessary by a closed-loop cooling system. This paper describes the concept of cryogenic design for this unique system. The amount of cryogenic loads and required mass flow rate are estimated by a relevant analysis. The effects of the helium II volume and the gap of safety valve on the cool-down time and temperature rising during off-normal state are also discussed.

Documents disponibles

Format PDF

Pages : 2006-3/ICEC II-B1

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Design of cryogenic cooling system for 21 T FT-ICR magnets.
  • Identifiant de la fiche : 2008-1502
  • Langues : Anglais
  • Source : Multiconference CryoPrague 2006 (9th Cryogenics 2006, ICEC 21, ICMC'06)
  • Date d'édition : 17/07/2006

Liens


Voir d'autres communications du même compte rendu (142)
Voir le compte rendu de la conférence