Diminution de la formation de givre sur une pompe à chaleur air-air à l'aide d'une méthode de dégivrage par bipasse de gaz chaud.

Frost retardation of an air-source heat pump by the hot gas bypass method.

Auteurs : BYUN J. S., LEE J., JEON C. D.

Type d'article : Article, Article de la RIF

Résumé

This study is concerned with a hot gas (refrigerant) bypass method to retard the formation and propagation of frost in an air-source heat pump. The feasibility of the hot gas bypass method was investigated experimentally and the method's performance is compared with that of a normal, 1.12 kW capacity air-source heat pump system with no defrost equipment such as an electric resistance heater. Results indicate that the hot gas bypass method is useful for retarding the formation and growth of frost at the outdoor coil. The best performance is shown under a bypass refrigerant flow rate of 0.2 kg/min (20% of the whole system refrigerant flow rate). During 210 min of heat pump operation, the hot gas bypass method improved COP and heating capacity at an average of 8.5 and 5.7%, respectively, relative to the normal system.

Documents disponibles

Format PDF

Pages : 328-334

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Frost retardation of an air-source heat pump by the hot gas bypass method.
  • Identifiant de la fiche : 2008-0854
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 31 - n. 2
  • Date d'édition : 03/2008

Liens


Voir d'autres articles du même numéro (17)