IIR document

Frost retardation of an air-source heat pump by the hot gas bypass method.

Author(s) : BYUN J. S., LEE J., JEON C. D.

Type of article: Article, IJR article

Summary

This study is concerned with a hot gas (refrigerant) bypass method to retard the formation and propagation of frost in an air-source heat pump. The feasibility of the hot gas bypass method was investigated experimentally and the method's performance is compared with that of a normal, 1.12 kW capacity air-source heat pump system with no defrost equipment such as an electric resistance heater. Results indicate that the hot gas bypass method is useful for retarding the formation and growth of frost at the outdoor coil. The best performance is shown under a bypass refrigerant flow rate of 0.2 kg/min (20% of the whole system refrigerant flow rate). During 210 min of heat pump operation, the hot gas bypass method improved COP and heating capacity at an average of 8.5 and 5.7%, respectively, relative to the normal system.

Available documents

Format PDF

Pages: 328-334

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Frost retardation of an air-source heat pump by the hot gas bypass method.
  • Record ID : 2008-0854
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 31 - n. 2
  • Publication date: 2008/03

Links


See other articles in this issue (17)
See the source