Document IIF

[Distribution] de frigorigène diphasique dans un collecteur intermédiaire d’un échangeur de chaleur à écoulements parallèles [dans des] minicanaux.

Two-phase refrigerant distribution in an intermediate header of a parallel flow minichannel heat exchanger.

Auteurs : BYUN H. W., KIM N. H.

Type d'article : Article, Article de la RIF

Résumé

Refrigerant R-410A distribution in a two pass evaporator with intermediate header was investigated. The number of tubes was 10 for the first pass and 12 for the second pass. Tests were conducted for the mass flux from 73 to 143?kg?m-2?s-1, quality from 0.4 to 0.6. In the intermediate header, two-phase mixture out of the first pass is merged and then re-distributed to the second pass. More liquid is forced downstream as mass flux or quality increases yielding better flow distribution. Effect of insertion device in the inlet header was also investigated. Efforts were made to develop correlations to predict the liquid or gas distribution in a header with limited success. Header pressure drop data are also provided.

Documents disponibles

Format PDF

Pages : 14-28

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Two-phase refrigerant distribution in an intermediate header of a parallel flow minichannel heat exchanger.
  • Identifiant de la fiche : 30016267
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 59