Effet de la configuration sur les connexions ascendantes d'un frigorigène diphasique dans un échangeur de chaleur à écoulement parallèle.
Effect of inlet configuration on upward branching of two-phase refrigerant in a parallel flow heat exchanger.
Auteurs : KIM N. H., BYUN H. W.
Type d'article : Article, Article de la RIF
Résumé
The refrigerant R134a flow distributions were experimentally studied for a round header-10 flat tube test section simulating a brazed aluminum heat exchanger. Three different inlet orientations (parallel, normal, vertical) were investigated. Tests were conducted with upward flow for the mass flux from 70 to 130 kg m-2 s-1 and quality from 0.2 to 0.6. Tubes were flush-mounted in the header with no protrusion. Both for liquid and gas, the best flow distribution was obtained from vertical inlet configuration. Between other two inlet configurations, parallel inlet was better for liquid distribution, and normal inlet was better for gas distribution. In general, the effect of mass flux or quality on flow distribution was not significant. Correlations were developed to predict the fraction of liquid or gas taken off by downstream channel as a function of header liquid Reynolds number at immediate upstream. Header pressure drop was obtained by subtracting appropriate pressure drops from the measured pressure drop. The header pressure drops were mostly negative, which implied that the pressure was recovered in the header.
Documents disponibles
Format PDF
Pages : 1062-1077
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Effect of inlet configuration on upward branching of two-phase refrigerant in a parallel flow heat exchanger.
- Identifiant de la fiche : 30008037
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 36 - n. 3
- Date d'édition : 05/2013
Liens
Voir d'autres articles du même numéro (51)
Voir la source
Indexation
-
Investigation on the gas-liquid two-phase flow ...
- Auteurs : XIE P., SATO R., SAKAMOTO N., et al.
- Date : 16/08/2015
- Langues : Anglais
- Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
- Formats : PDF
Voir la fiche
-
Effect of inlet configuration on the two-phase ...
- Auteurs : KIM D. Y., KIM N. H., BYUN H. W., et al.
- Date : 07/06/2010
- Langues : Anglais
- Source : ACRA2010. Asian conference on refrigeration and air conditioning: Tokyo, Japan, June 7-9, 2010.
- Formats : PDF
Voir la fiche
-
The experimental study of two-phase flow distri...
- Auteurs : ONAKA Y., LI J., MATSUMOTO T., et al.
- Date : 23/04/2017
- Langues : Anglais
- Source : 5th IIR Conference on Thermophysical Properties and Transfer Processes of Refrigerants.
- Formats : PDF
Voir la fiche
-
Visualization of two-phase refrigerant flow in ...
- Auteurs : LI W., HRNJAK P.
- Date : 11/2021
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 131
- Formats : PDF
Voir la fiche
-
Refrigerant distribution characteristics in ver...
- Auteurs : ENDOH K.
- Date : 11/07/2016
- Langues : Anglais
- Source : 2016 Purdue Conferences. 16th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche