Recommandé par l'IIF / Document IIF
Écoulement d'air pour disperser les fuites de frigorigénes des systémes frigorifiques à hydrocarbures.
Airflow to disperse refrigerant leaks from hydrocarbon refrigeration systems.
Type d'article : Article de la RIF
Résumé
Whilst R290 is currently used to a limited extent in room air conditioners there is a desire for wider application due to its excellent performance and negligible global warming potential. The product standard IEC 60335–2–40 specifies requirements to limit the allowable refrigerant charge in such a way that it obstructs the wider use of R290. Airflow of an indoor unit can be used to dilute a refrigerant leak, enabling substantially greater charge quantities to be used. A numerical model based on entrainment theory was developed and supported by analysing the behaviour of experimentally simulated releases under various conditions with indoor unit airflow. The work determines the minimum airflow rate necessary to prevent formation of a flammable concentration within the room. Further, the work includes determination of appropriate response time and leak rate to initiate airflow once a leak has begun. The developed methodology can equally be applied to commercial refrigeration units and other flammable refrigerants.
Documents disponibles
Format PDF
Pages : 220-229
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Airflow to disperse refrigerant leaks from hydrocarbon refrigeration systems.
- Identifiant de la fiche : 30029541
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 137
- Date d'édition : 05/2022
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2022.02.008
- Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.
Liens
Voir d'autres articles du même numéro (23)
Voir la source
Indexation
-
Assessment of factors affecting R290 concentrat...
- Auteurs : COLBOURNE D., SUEN K. O.
- Date : 18/06/2018
- Langues : Anglais
- Source : 13th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2018). Proceedings. Valencia, Spain, June 18-20th 2018.
- Formats : PDF
Voir la fiche
-
R290 leakage hazards assessment of a 1 HP split...
- Auteurs : NING Q., HE G., SUN W., FAN M., LI X., HONG Z.
- Date : 07/2022
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 139
- Formats : PDF
Voir la fiche
-
Indoor leakage test for safety of R-290 split t...
- Auteurs : LI T.
- Date : 04/2014
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 40
- Formats : PDF
Voir la fiche
-
Study on risk assessment of air conditioner usi...
- Auteurs : BABA A., TAKAICHI K., TAIRA S., et al.
- Date : 24/08/2019
- Langues : Anglais
- Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
Voir la fiche
-
Minimum airflow rates to dilute R290 concentrat...
- Auteurs : COLBOURNE D., SUEN K. O.
- Date : 18/06/2018
- Langues : Anglais
- Source : 13th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2018). Proceedings. Valencia, Spain, June 18-20th 2018.
- Formats : PDF