Effect of inlet configuration on upward branching of two-phase refrigerant in a parallel flow heat exchanger.

Author(s) : KIM N. H., BYUN H. W.

Type of article: Article, IJR article

Summary

The refrigerant R134a flow distributions were experimentally studied for a round header-10 flat tube test section simulating a brazed aluminum heat exchanger. Three different inlet orientations (parallel, normal, vertical) were investigated. Tests were conducted with upward flow for the mass flux from 70 to 130 kg m-2 s-1 and quality from 0.2 to 0.6. Tubes were flush-mounted in the header with no protrusion. Both for liquid and gas, the best flow distribution was obtained from vertical inlet configuration. Between other two inlet configurations, parallel inlet was better for liquid distribution, and normal inlet was better for gas distribution. In general, the effect of mass flux or quality on flow distribution was not significant. Correlations were developed to predict the fraction of liquid or gas taken off by downstream channel as a function of header liquid Reynolds number at immediate upstream. Header pressure drop was obtained by subtracting appropriate pressure drops from the measured pressure drop. The header pressure drops were mostly negative, which implied that the pressure was recovered in the header.

Available documents

Format PDF

Pages: 1062-1077

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Effect of inlet configuration on upward branching of two-phase refrigerant in a parallel flow heat exchanger.
  • Record ID : 30008037
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 36 - n. 3
  • Publication date: 2013/05