Document IIF

Efficacité et vitesse optimale du jet pour un rideau d'air à jet d'air plan utilisé afin de réduire l'infiltration dans une chambre froide.

Effectiveness and optimum jet velocity for a plane jet air curtain used to restrict cold room infiltration.

Auteurs : FOSTER A. M., SWAIN M. J., BARRETT R., et al.

Type d'article : Article, Article de la RIF

Résumé

The effectiveness of a 1.0-m wide air curtain fitted over a 1.36-m wide entrance to a cold store has been evaluated. It is shown that careful setting up of the air curtain (adjusting the jet velocity and angle) was needed ; this achieved an effectiveness of 0.77 compared to the initial value of only 0.31 as set by the installer. An analytical model to predict the optimum jet velocity was compared to measured data. It is important to choose the correct safety factor (an increase in the jet velocity) for this model, as an effectiveness of between 0.37 and 0.70 could be produced using the range of safety factors found in the literature. A 2D computational fluid dynamics model predicted a maximum effectiveness of 0.84 and showed how the effectiveness of the curtain was related to the shape of the jet and how this varied with jet velocity and door opening duration.

Documents disponibles

Format PDF

Pages : 692-699

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Effectiveness and optimum jet velocity for a plane jet air curtain used to restrict cold room infiltration.
  • Identifiant de la fiche : 2006-1901
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 29 - n. 5
  • Date d'édition : 08/2006

Liens


Voir d'autres articles du même numéro (16)
Voir la source