IIR document

Effectiveness and optimum jet velocity for a plane jet air curtain used to restrict cold room infiltration.

Author(s) : FOSTER A. M., SWAIN M. J., BARRETT R., et al.

Type of article: Article, IJR article

Summary

The effectiveness of a 1.0-m wide air curtain fitted over a 1.36-m wide entrance to a cold store has been evaluated. It is shown that careful setting up of the air curtain (adjusting the jet velocity and angle) was needed ; this achieved an effectiveness of 0.77 compared to the initial value of only 0.31 as set by the installer. An analytical model to predict the optimum jet velocity was compared to measured data. It is important to choose the correct safety factor (an increase in the jet velocity) for this model, as an effectiveness of between 0.37 and 0.70 could be produced using the range of safety factors found in the literature. A 2D computational fluid dynamics model predicted a maximum effectiveness of 0.84 and showed how the effectiveness of the curtain was related to the shape of the jet and how this varied with jet velocity and door opening duration.

Available documents

Format PDF

Pages: 692-699

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Effectiveness and optimum jet velocity for a plane jet air curtain used to restrict cold room infiltration.
  • Record ID : 2006-1901
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 29 - n. 5
  • Publication date: 2006/08

Links


See other articles in this issue (16)
See the source