ESSAI EN LABORATOIRE D'UNE POMPE A CHALEUR UTILISANT UN MELANGE DE R13B1 ET DE R152A.

LABORATORY TESTING OF A HEAT PUMP SYSTEM USING AN R13B1/R152A REFRIGERANT MIXTURE.

Auteurs : VINEYARD E. A.

Résumé

ON A EFFECTUE DES ESSAIS AVEC UN MELANGE NON AZEOTROPIQUE DE R13B1 ET DE R152A AFIN DE DETERMINER L'APTITUDE DE CE MELANGE A ASSURER UNE REGULATION DE LA PUISSANCE EN MODIFIANT LA COMPOSITION ET A PERMETTRE UNE AUGMENTATION DE PUISSANCE, PAR RAPPORT AU R22, A DES TEMPERATURES AMBIANTES BASSES. LE CHOIX D'UN TEL MELANGE POURRAIT AMELIORER LE RENDEMENT D'UNE POMPE A CHALEUR EN REDUISANT LES PERTES DUES A L'ALTERNANCE DES PERIODES DE FONCTIONNEMENT ET D'ARRET. LES RESULTATS DU MELANGE REVELENT UNE POSSIBILITE DE MODULATION DE PUISSANCE DE 3.643 WATTS A 264,7 K (-8,3 DEG C) A 2.506 WATTS A 281,3 K (8,3 DEG C) EN CHAUFFAGE ET DE 2.184 WATTS A 300,8 K (27,8 DEG C) A 2.693 WATTS A 308 K (35 DEG C) EN REFROIDISSEMENT. ON PRESENTE UNE ANALYSE DU COP POUR LE MELANGE ET SES COMPOSANTS PURS AINSI QU'UNE COMPARAISON AVEC LES RESULTATS OBTENUS AVEC DU R22.

Détails

  • Titre original : LABORATORY TESTING OF A HEAT PUMP SYSTEM USING AN R13B1/R152A REFRIGERANT MIXTURE.
  • Identifiant de la fiche : 1989-1145
  • Langues : Anglais
  • Date d'édition : 1988
  • Source : Source : ASHRAE Trans.
    vol. 94; n. 1; 292-303; 8 fig.; 4 tabl.; 4 ref.