LABORATORY TESTING OF A HEAT PUMP SYSTEM USING AN R13B1/R152A REFRIGERANT MIXTURE.
Author(s) : VINEYARD E. A.
Summary
TESTING WAS PERFORMED WITH A NON-AZEOTROPIC MIXTURE OF R13B1/R152A TO DETERMINE ITS ABILITY TO ACHIEVE CAPACITY CONTROL BY ADJUSTING THE COMPOSITION AND INCREASED CAPACITY, RELATIVE TO R22, AT LOW AMBIENT TEMPERATURES. THE SELECTION OF SUCH A MIXTURE COULD IMPROVE THE EFFICIENCY OF A HEAT PUMP BY DECREASING THE CYCLING LOSSES. RESULTS FOR THE MIXTURE SHOW A POTENTIAL CAPACITYMODULATION FROM 3,643 WATTS AT 264.7 K (-8.3 DEG C) TO 2,506 WATTS AT 281.3 K (8.3 DEG C) IN HEATING AND FROM 2,184 WATTS AT 300.8 K (27.8 DEG C) TO 2,693 WATTS AT 308 K (35 DEG C) IN COOLING. AN ANALYSIS OF THE COP FOR THE MIXTURE AND ITS PURE COMPONENTS IS PRESENTED ALONG WITH A COMPARISON AGAINST RESULTS OBTAINED WITH R22.
Details
- Original title: LABORATORY TESTING OF A HEAT PUMP SYSTEM USING AN R13B1/R152A REFRIGERANT MIXTURE.
- Record ID : 1989-1145
- Languages: English
- Publication date: 1988
- Source: Source: ASHRAE Trans.
vol. 94; n. 1; 292-303; 8 fig.; 4 tabl.; 4 ref. - Document available for consultation in the library of the IIR headquarters only.
Indexing
- Themes: Heat pumps techniques
- Keywords: R22; R152a; R13b1; Heat pump; Zeotropic mixture; Testing; Refrigerant; Air conditioning
-
THE USE OF MIXED REFRIGERANTS IN AIR TO AIR HEA...
- Author(s) : COOPER W. D.
- Date : 1982
- Languages : English
View record
-
TESTING AND MODELLING OF A WATER-TO-AIR HEAT PU...
- Author(s) : PARENT D., LARUE P. A.
- Date : 1989
- Languages : English
View record
-
SIMULATION OF A HEAT PUMP OPERATING WITH A NON-...
- Author(s) : DOMANSKI P. A., DIDION D. A.
- Date : 1985
- Languages : English
View record
-
EXPERIMENTAL EVALUATION OF A HEAT PUMP AIR COND...
- Author(s) : MINATO K., MATSUKI K.
- Date : 1990/03/12
- Languages : English
View record
-
AIR-TO-AIR HEAT PUMP PERFORMANCE WITH THREE DIF...
- Author(s) : GALLOWAY J. E., GOLDSCHMIDT V. W.
- Date : 1991
- Languages : English
View record