Document IIF

Etude de l'amélioration de l'efficacité du fonctionnement des climatiseurs en exploitation tout au long de l'année (effet du taux de compression minimal toléré et de la capacité du détendeur).

Study on efficiency improvement of packaged air conditioners for year round cooling (effects of allowable minimum compression ratio and expansion valve capacity).

Résumé

Focusing on air conditioners used for year-round cooling, high-efficiency operation at times of low outdoor air temperature can be achieved by lowering the condensing pressure and operating at a low compression ratio. A year-round cooling air conditioner was constructed, and a performance test showed that the COP of the compression cycle could exceed 10 at maximum for an outdoor air temperature of 0 °C. This air conditioner was deployed for one year in Tokyo in the same cooling-load environment: power consumption decreased by about 40% over the year.