Etude de la ventilation dans les salles d'opération grâce à la dynamique numérique des fluides (CFD).
Estudio de la ventilación en quirófanos mediante dinamica de fluidos computacional.
Auteurs : GARCÍA GÁFARO C., MVUAMA M. C., SALA LIZARRAGA J. M., et al.
Résumé
This paper reflects the results and conclusions of a study on the air's motion in four old surgery rooms in a Basque Country (Spain) hospital that were to be reformed. Its purpose was to understand the airflow trajectory in the surgery rooms, to detect the turbulence zones and to evaluate the efficiency of the system in order to suggest appropriate improvements to guide the Maintenance Department of the Hospital to undertake the improvements of the air-fanning. The methodology followed was based on simulating by CFD the existing ventilation system and analyzing an improved system in the following four situations: watertight doors, no watertight doors, and surgery rooms with two additional extract (exhaust) grilles with watertight or no watertight doors. In all cases, the lack of the water tightness in the doors produced a short-circuit in ventilation's flow ranging from 25 to 83% of the indoor airflow.
Détails
- Titre original : Estudio de la ventilación en quirófanos mediante dinamica de fluidos computacional.
- Identifiant de la fiche : 2008-1334
- Langues : Espagnol
- Date d'édition : 20/11/2006
- Source : Source : Climamed 2006, Lyon
PIV-3.2; 427-435; fig.; tabl.; 7 ref.
Indexation
- Thèmes : Autres équipements de conditionnement d'air
- Mots-clés : CFD; Air; Simulation; Salle d'opération; Hôpital; Écoulement; Conditionnement d'air
-
Wirtschaftlichkeitsvergleich von Operationsraum...
- Auteurs : KÜLPMANN R., MEIERHANS R.
- Date : 03/2001
- Langues : Allemand
- Source : KI Luft Kältetech. - n. 3
Voir la fiche
-
Flow regimes and thermal patterns in air-condit...
- Auteurs : KHALIL E. E.
- Date : 20/11/2006
- Langues : Anglais
Voir la fiche
-
Three-dimensional analysis for hospital operati...
- Auteurs : HO S. H., ROSARIO L., RAHMAN M. M.
- Date : 07/2009
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 29 - n. 10
Voir la fiche
-
Comparison of operating room ventilation system...
- Auteurs : MEMARZADEH F., MANNING A. P.
- Date : 2002
- Langues : Anglais
- Source : ASHRAE Transactions. 2002 annual Meeting, Honolulu, Hawaii. Volume 108, part 2 + CD-ROM.
Voir la fiche
-
Théorie de la zone d'écoulement principale : le...
- Auteurs : XU Z., SHEN J., MEI Z., et al.
- Date : 10/2001
- Langues : Chinois
- Source : HV & AC - vol. 31 - n. 142
Voir la fiche