Étude du fractionnement de la composition du R452B ou du DR55 comme substituts au R410A et de leur impact sur l’inflammabilité et sur les mesures de sécurité.
Compositional fractionation studies of R410A alternative R452B or DR55 and their impact on flammability behavior and safety implications.
Numéro : pap. 2122
Auteurs : KUJAK S., SCHULTE K.
Résumé
Today air conditioning product and applications designers, as a result of climate change contribution concerns for high direct global warming potential (GWP) refrigerants, are being asked to consider lower GWP refrigerants with various degrees of flammability. In recent year, the HVACR industry has been actively investigating the safety of flammable refrigerants by determining their risks, potential occurrences and severity of events. Today R410A is used to cover most air conditioning applications and all lower GWP alternatives presented to date have some degree of flammability with most being ASHRAE 34 flammability class 2L. A novel R410A alternative refrigerant blend, R452B or DR55, has recently been studied in a 4 ton RTU to determine the potential for compositional fractionation in various modes of operation. In addition, the ASHRAE flammability process needed to classify refrigerant flammability and flammability classification data for R452B will be presented in this paper. The unit compositional data and the ASHRAE classification process and data will be compared and contrasted to show differences in potential flammability interpretations and design safety implications.
Documents disponibles
Format PDF
Pages : 8
Disponible
Prix public
20 €
Prix membre*
15 €
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Compositional fractionation studies of R410A alternative R452B or DR55 and their impact on flammability behavior and safety implications.
- Identifiant de la fiche : 30018894
- Langues : Anglais
- Source : 2016 Purdue Conferences. 16th International Refrigeration and Air-Conditioning Conference at Purdue.
- Date d'édition : 11/07/2016
Liens
Voir d'autres communications du même compte rendu (274)
Voir le compte rendu de la conférence
Indexation
-
An empirical model for refrigerant flammability...
- Auteurs : LINTERIS G. T., BELL I. H., MCLINDEN M. O.
- Date : 08/2019
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 104
- Formats : PDF
Voir la fiche
-
Safety related properties of low-GWP refrigerants.
- Auteurs : ASKAR E., SCHRODER V., GÖPFERT T., et al.
- Date : 24/08/2019
- Langues : Anglais
- Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
Voir la fiche
-
Review of methodology to set safety factors for...
- Auteurs : HANSEN B., KUJAK S.
- Date : 09/2018
- Langues : Anglais
- Source : 1st IIR international conference on the application of HFO refrigerants, Birmingham, September 2-5 2018.
- Formats : PDF
Voir la fiche
-
Review of methodology to set safety factors for...
- Auteurs : KUJAK S., HANSEN B.
- Date : 09/2018
- Langues : Anglais
- Source : 1st IIR international conference on the application of HFO refrigerants, Birmingham, September 2-5 2018.
- Formats : PDF
Voir la fiche
-
Development, testing and evaluation of 2L refri...
- Auteurs : LOW R., PROUST C.
- Date : 09/2018
- Langues : Anglais
- Source : 1st IIR international conference on the application of HFO refrigerants, Birmingham, September 2-5 2018.
- Formats : PDF
Voir la fiche