Etude expérimentale d'un système en cascade NH3/CO2 et comparaison avec un système au R-404A dans les systèmes de supermarchés.

Experimental investigation of NH3/CO2 cascade system and comparison with R-404A system for supermarket refrigeration.

Résumé

This study investigates the performance of an NH3/CO2 cascade system for supermarket refrigeration application in a laboratory environment. The tested CO2 system is designed and scaled to fulfill the requirements of an average size supermarket in Sweden. Possibility for hot gas defrost in the freezers has been investigated and compared to the conventional electric heaters defrost method. Two cascade condenser arrangements have been evaluated. The cascade system has been compared to R-404A system installed in the same laboratory. The results show that connecting the cascade condenser via thermosiphon or hot gas de-superheat arrangements yields good system stability and heat transfer performance. Hot gas defrost successfully defrosted the freezer evaporator but with long period and higher energy consumption compared to the conventional electric defrost method. The tested cascade system had up to 60% higher total COP compared to the R-404A system installed in laboratory.

Documents disponibles

Format PDF

Pages : ICR07-B2-463

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental investigation of NH3/CO2 cascade system and comparison with R-404A system for supermarket refrigeration.
  • Identifiant de la fiche : 2007-2661
  • Langues : Anglais
  • Source : ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
  • Date d'édition : 21/08/2007

Liens


Voir d'autres communications du même compte rendu (839)
Voir le compte rendu de la conférence