Étude expérimentale d'une paire charbon actif-R723 pour utilisation dans des systèmes de pompe à chaleur et de froid à adsorption.

Experimental investigation of activated carbon-R723 pair for use in adsorption heat pump and refrigeration systems.

Numéro : pap. n. 28

Auteurs : LYCHNOS G., TAMAINOT-TELTO Z.

Résumé

The physical behavior of the new refrigerant R723, an azeotropic mixture of 60% Ammonia and 40% Dimethyl Ether, was investigated for use in adsorption heat pumps and refrigeration systems. The potential use of this refrigerant blend in adsorption systems with components made of copper instead of stainless steel provides with a motive for experimental investigation. In this work the experimental results of an activated carbon – R723 pair generator are presented when operating with driving temperatures ranging from 100°C up to 170°C and condensing temperatures of 20°C and 35°C. By comparing the measured temperature of the refrigerant liquid in the receiver and the saturated temperature calculated from the measured pressure it is shown that the refrigerant R723 remains stable throughout the adsorption – desorption process even when operating at pressures as high as 16 bar.

Documents disponibles

Format PDF

Pages : 6 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental investigation of activated carbon-R723 pair for use in adsorption heat pump and refrigeration systems.
  • Identifiant de la fiche : 30013457
  • Langues : Anglais
  • Source : International sorption heat pump conference (ISHPC2014), College Park, United States, March 31-April 2, 2014.
  • Date d'édition : 02/03/2014

Liens


Voir d'autres communications du même compte rendu (125)
Voir le compte rendu de la conférence