Étude expérimentale de la performance thermique d'un puits thermique de caloduc à tubes plats pour le refroidissement multi-puces.

[In Chinese. / En chinois.]

Auteurs : HAN X., TIAN Z., HE W., et al.

Type d'article : Article

Résumé

A novel plat heat pipe heat sink for multi-chip was designed, and the thermal performance of the heat sink in different air speed, chips numbers and positions, heating power was experimentally investigated. The experimental results showed that the maximum heat transport capacity of the heat sink with one, two and three heat sources were 310W, 390 W and 500 W respectively in the horizontal position, and 275 W, 408 W, 500 W in the vertical application when the chips temperature was less than 80°C and the ambient temperature was 20°C. For the flat heat pipe heat sink, multiple chips cooling can dissipate more heat than unique source. The results were found to agree well with the experimental data about the thermal spreading effect of the flat heat pipe. It was shown that flat heat pipe accords with the requirements of electronic devices cooling.

Documents disponibles

Format PDF

Pages : 52-56

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails


Liens


Voir d'autres articles du même numéro (6)
Voir la source