Document IIF

Étude sur les performances d'un système de prétraitement d'air neuf intégré dans des enveloppes avec tuyauteries encastrées et utilisant de l'énergie géothermique peu profonde.

Performance investigation of a fresh air pre-handling system integrated with pipe-embedded envelopes by utilizing shallow geothermal energy.

Numéro : pap. n. 1566

Auteurs : LYU W., LI X., YAN S.

Résumé

Traditionally, shallow geothermal energy is utilized by ground source heat pump. Actually, the temperature of shallow geothermal energy is much suitable for the cooling/heating of the building envelope and fresh air in most of time. To utilize shallow geothermal energy more efficiently, an integrated system combined pipe-embedded walls, pipe-embedded windows, and fresh air prehandling
system is proposed based on the temperature comparison among the indoor air, envelopes, fresh air and the undisturbed soil. The simulation model of the integrated system is developed on the platform of TRNSYS. The free-running temperature of the integrated system applied in an office building in Shanghai is investigated. The results show that the free-running temperature of the
integrated system is always higher than 15 °C throughout the year, the free-running temperature that higher than 30 °C accounts for a fewer ratio and the non-air conditioning period extends approximately 20% compared with the conventional GSHP system.

Documents disponibles

Format PDF

Pages : 8

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance investigation of a fresh air pre-handling system integrated with pipe-embedded envelopes by utilizing shallow geothermal energy.
  • Identifiant de la fiche : 30026793
  • Langues : Anglais
  • Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
  • Date d'édition : 24/08/2019
  • DOI : http://dx.doi.org/10.18462/iir.icr.2019.1566

Liens


Voir d'autres communications du même compte rendu (632)
Voir le compte rendu de la conférence