Document IIF

Evaluation de la performance d'un compresseur biétagé au CO2.

Performance evaluation of a two-stage carbon dioxide compressor.

Résumé

This paper provides the performance of a two-stage carbon dioxide compressor. Measurements were taken of the temperatures, pressures, mass flow rate, the RPM and the power consumption of the compressor and the cooling capacity of the evaporator. The characteristic performance values have been calculated through an approached gas cooler outlet temperature and an isenthalpic expansion. The calculated values are the volumetric efficiency, the compressor efficiency, the COP and the capacity. Based on these measurements, the performance of the compressor is determined. The volumetric efficiency ranged between 0.41 and 0.84 and the compressor efficiency was as large as 0.58. In order to better characterize the compressor and to provide compressor performance, compressor maps were provided differently from the conventional compressor performance maps.

Documents disponibles

Format PDF

Pages : 2004-2

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance evaluation of a two-stage carbon dioxide compressor.
  • Identifiant de la fiche : 2005-1794
  • Langues : Anglais
  • Source : Natural Working Fluids 2004: 6th IIR-Gustav Lorentzen Conference
  • Date d'édition : 01/08/2004

Liens


Voir d'autres communications du même compte rendu (105)
Voir le compte rendu de la conférence