EVALUATION DES AVANTAGES ET DES INCONVENIENTS DU SOUS-REFROIDISSEMENT.

EVALUATING THE PROS AND CONS OF SUBCOOLING.

Auteurs : ARES R.

Type d'article : Article

Résumé

DANS UN LABORATOIRE D'ESSAI AMERICAIN, ON A EFFECTUE DES EXPERIENCES SUR UN SYSTEME OPERANT DANS UN SUPERMARCHE AFIN DE DETERMINER LES AVANTAGES PRATIQUES DU SOUS-REFROIDISSEMENT DU FRIGORIGENE CONDENSE. LES RESULTATS ONT MONTRE QU'AVEC UN LIQUIDE SOUS-REFROIDI, MAINTENU A UNE TEMPERATURE DE 278 A 279 K (5 A 6 DEG C), L'AUGMENTATION GLOBALE DU RENDEMENT DE L'INSTALLATION EST DE L'ORDRE DE 21,5 % LORSQUE LA PRESSION DE CONDENSATION CORRESPOND A UNE TEMPERATURE DE VAPEUR SATUREE DE 300 K (27 DEG C) ; IL TOMBE A 3 % A 288 K (15 DEG C). DANS UN SUPERMARCHE TYPE PRESENTANT UN SYSTEME A DEUX TEMPERATURES, LE SOUS-REFROIDISSEMENT EST OBTENU PARTIELLEMENT DANS UNE BATTERIE REFROIDIE PAR L'AIR AMBIANT DANS UN CONDENSEUR EVAPORATIF ET, PARTIELLEMENT, PAR EVAPORATION DU FRIGORIGENE DANS UN ECHANGEUR MONTE A L'ASPIRATION DU COMPRESSEUR < HAUTE TEMPERATURE >. D.W.H.

Détails

  • Titre original : EVALUATING THE PROS AND CONS OF SUBCOOLING.
  • Identifiant de la fiche : 1989-1954
  • Langues : Anglais
  • Source : Air Cond. Heat. Refrig. News - vol. 175 - n. 12
  • Date d'édition : 21/11/1988
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir la source