Évaluation du R-438A comme frigorigène de conversion immédiate du R-22 dans un refroidisseur d'eau à détente directe.
Assessment of R-438A as a retrofit refrigerant for R-22 in direct expansion water chiller.
Auteurs : ELGENDY E., HASSANAIN M., FATOUH M.
Type d'article : Article, Article de la RIF
Résumé
The present work aims to evaluate the performance characteristics of a vapor compression refrigeration system using R-438A as a retrofit refrigerant for R-22. In order to achieve this objective, a test facility is developed and experiments are performed over a wide range of chilled water inlet temperature (11:20 °C), condenser water inlet temperature (25:35 °C) and condenser water mass flow rate (363:543 kg h-1). Results showed that as the chilled water inlet temperature changes from 11.5 to 20.5 °C, system COP increases from 1.78 to 2.07 at constant condenser water inlet temperature of 25.5 °C. Cooling capacity and COP of the system using R-438A are lower than R-22 by 11% and 12.5%, respectively. However, compressor discharge temperature using R-438A is slightly lower than R-22 which confirms that R-438A can be used as a retrofit refrigerant for R-22 to complete the remaining life time of the existing plants.
Documents disponibles
Format PDF
Pages : 127-136
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Assessment of R-438A as a retrofit refrigerant for R-22 in direct expansion water chiller.
- Identifiant de la fiche : 30013122
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 50
- Date d'édition : 02/2015
Liens
Voir d'autres articles du même numéro (20)
Voir la source
Indexation
-
Direct expansion or chilled water. Which is bet...
- Auteurs : NALL D. H.
- Date : 09/2016
- Langues : Anglais
- Source : ASHRAE Journal - vol. 58 - n. 9
Voir la fiche
-
State-space model for dynamic behavior of vapor...
- Auteurs : YAO Y., HUANG M., CHEN J.
- Date : 12/2013
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 36 - n. 8
- Formats : PDF
Voir la fiche
-
Experimental evaluation of HCFC-22 replacement ...
- Auteurs : LLOPIS R., CABELLO R., SÁNCHEZ D., et al.
- Date : 05/2011
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 31 - n.6-7
Voir la fiche
-
A reduced global warming potential replacement ...
- Auteurs : KONTOMARIS K., KULANKARA S., KAUFFMAN J. P.
- Date : 10/2013
- Langues : Anglais
- Source : HVAC&R Research - vol. 19 - n. 7
Voir la fiche
-
Expérience sur l'effet du retour de frigorigène...
- Auteurs : HAN L., TAO L., ZHENG Z., et al.
- Date : 08/2010
- Langues : Chinois
- Source : Journal of Refrigeration - vol. 31 - n. 4
- Formats : PDF
Voir la fiche