IIR document
Assessment of R-438A as a retrofit refrigerant for R-22 in direct expansion water chiller.
Author(s) : ELGENDY E., HASSANAIN M., FATOUH M.
Type of article: Article, IJR article
Summary
The present work aims to evaluate the performance characteristics of a vapor compression refrigeration system using R-438A as a retrofit refrigerant for R-22. In order to achieve this objective, a test facility is developed and experiments are performed over a wide range of chilled water inlet temperature (11:20 °C), condenser water inlet temperature (25:35 °C) and condenser water mass flow rate (363:543 kg h-1). Results showed that as the chilled water inlet temperature changes from 11.5 to 20.5 °C, system COP increases from 1.78 to 2.07 at constant condenser water inlet temperature of 25.5 °C. Cooling capacity and COP of the system using R-438A are lower than R-22 by 11% and 12.5%, respectively. However, compressor discharge temperature using R-438A is slightly lower than R-22 which confirms that R-438A can be used as a retrofit refrigerant for R-22 to complete the remaining life time of the existing plants.
Available documents
Format PDF
Pages: 127-136
Available
Public price
20 €
Member price*
Free
* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).
Details
- Original title: Assessment of R-438A as a retrofit refrigerant for R-22 in direct expansion water chiller.
- Record ID : 30013122
- Languages: English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 50
- Publication date: 2015/02
Links
See other articles in this issue (20)
See the source
Indexing
-
Themes:
Compression systems;
HCFCs;
HFCs;
Chillers - Keywords: Refrigerating system; Direct expansion; Drop-in; Chiller; R22; Substitute; Performance; Expérimentation; Refrigerant; Air conditioning
-
Experimental evaluation of HCFC-22 replacement ...
- Author(s) : LLOPIS R., CABELLO R., SÁNCHEZ D., et al.
- Date : 2011/05
- Languages : English
- Source: Applied Thermal Engineering - vol. 31 - n.6-7
View record
-
Direct expansion or chilled water. Which is bet...
- Author(s) : NALL D. H.
- Date : 2016/09
- Languages : English
- Source: ASHRAE Journal - vol. 58 - n. 9
View record
-
Drop-in energy performance evaluation of R1234y...
- Author(s) : MOTA BABILONI A., NAVARRO-ESBRÍ J., BARRAGÁN A., et al.
- Date : 2014/10
- Languages : English
- Source: Applied Thermal Engineering - vol. 71 - n. 1
View record
-
Energy and exergy analyses of R513a as a R134a ...
- Author(s) : SUN J., LI W., CUI B.
- Date : 2020/04
- Languages : English
- Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 112
- Formats : PDF
View record
-
Experimental analysis of the internal heat exch...
- Author(s) : NAVARRO-ESBRÍ J., MOLÉS F., BARRAGÁN-CERVERA A.
- Date : 2013/09
- Languages : English
- Source: Applied Thermal Engineering - vol. 59 - n. 1-2
View record