Evaluation expérimentale de l'effet de la ventilation sur la performance d'un système à débit variable en mode de refroidissement. I. Evaluation expérimentale.

Experimental evaluation of the ventilation effect on the performance of a VRV system in cooling mode. I. Experimental evaluation.

Auteurs : AYNUR T. N., HWANG Y., RADERMACHER R.

Type d'article : Article

Résumé

The effect of ventilation on indoor temperature control, thermal comfort, outdoor unit energy consumption, and efficiency of the multi-split variable refrigerant volume (VRV) system is investigated in a field test under varying outdoor conditions. It is observed through the experiments that ventilation does not affect the indoor temperature control of the multi-split VRV system; instead it increases the indoor humidity ratio, resulting in a less comfortable indoor environment. Even though ventilation increases the outdoor unit energy consumption due to the ventilation load, it does not have a considerable effect on the efficiency of the multi-split VRV system.

Détails

  • Titre original : Experimental evaluation of the ventilation effect on the performance of a VRV system in cooling mode. I. Experimental evaluation.
  • Identifiant de la fiche : 2009-0333
  • Langues : Anglais
  • Source : HVAC&R Research - vol. 14 - n. 4
  • Date d'édition : 07/2008