FONCTIONNEMENT PAR TOUT OU RIEN D'UN SYSTEME FRIGORIFIQUE A COMPRESSEUR A PISTON ET TUBE CAPILLAIRE.

THE ON/OFF OPERATION IN A RECIPROCATING COMPRESSOR REFRIGERATION SYSTEM WITH CAPILLARY.

Auteurs : WANG J., WU Y.

Résumé

DANS LES PETITES INSTALLATIONS A TUBE CAPILLAIRE, LE COMPRESSEUR DEMARRE ET S'ARRETE FREQUEMMENT. APRES ARRET, LES PRESSIONS DU CONDENSEUR ET DE L'EVAPORATEUR SONT EN EQUILIBRE. LORSQUE LE COMPRESSEUR REDEMARRE, IL Y A UN TEMPS DE LATENCE AVANT DE RECONSTITUER LES PRESSIONS NECESSAIRES DU CONDENSEUR ET DE L'EVAPORATEUR. LES AUTEURS ONT ETUDIE LE FONCTIONNEMENT D'UNE INSTALLATION DE 3,48 KILOWATTS ET NOTAMMENT L'INFLUENCE DE LA MIGRATION DU FRIGORIGENE AU COURS DE L'ARRET SUR LA PRESSION, LA TEMPERATURE ET LA CONSOMMATION D'ENERGIE. LES RESULTATS EXPERIMENTAUX INDIQUENT QUE SI ON EVITE LA MIGRATION DU FRIGORIGENE, LA CONSOMMATION D'ENERGIE PEUT ETRE REDUITE DE 4 % ET LA VALEUR DE POINTE DE LA CONSOMMATION D'ENERGIE DE 9,4 %. EN MEME TEMPS, LA PUISSANCE FRIGORIFIQUE POURRAIT ETRE AUGMENTEE.

Documents disponibles

Format PDF

Pages : 1988-2

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : THE ON/OFF OPERATION IN A RECIPROCATING COMPRESSOR REFRIGERATION SYSTEM WITH CAPILLARY.
  • Identifiant de la fiche : 1990-1018
  • Langues : Anglais
  • Date d'édition : 1988
  • Source : Source : C. R. Réun. Purdue, IIF/Proc. Purdue Meet., IIR
    1988-2; 165-173; 10 fig.; 4 ref.; discuss.