Formation de givre sur les évaporateurs à tubes ailettés munis de ventilateurs : analyse visuelle et numérique.

Frost formation on fan-supplied tube-fin evaporators: a visual and numerical analysis.

Numéro : pap. 2105

Auteurs : DA SILVA D. L.

Résumé

This paper presents an experimental and numerical study to evaluate the thermal-hydraulic performance of light commercial capacity evaporators operating under frosting conditions. A tube-fin heat exchanger was tested on a closed-loop wind-tunnel considering the fan performance. A visual analysis of the frost formation processes was carried out to compare the frost layer morphology in different conditions. A mathematical model was developed and the numerical results were compared with the experimental accumulated mass of frost, air flow rate and cooling capacity, with all the predictions falling within the experimental band of uncertainties. Based on this comparison, a frost density correlation was proposed for a typical range of light commercial refrigeration applications. The results show evaporator cooling capacity reductions up to 40% due to frost formation process. Moreover, the effects of air flow reduction and low conductivity frost layer on the overall thermal resistance were analyzed, when it was found that the former is the main cause of the cooling capacity reduction under frosting conditions.

Documents disponibles

Format PDF

Pages : 10 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Frost formation on fan-supplied tube-fin evaporators: a visual and numerical analysis.
  • Identifiant de la fiche : 30006212
  • Langues : Anglais
  • Source : 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
  • Date d'édition : 16/07/2012

Liens


Voir d'autres communications du même compte rendu (195)
Voir le compte rendu de la conférence